Leak Detection
For detecting the leaking tube, the following procedure is followed
- Discharge the liquid being cooled in the liquid chamber by the drain valve provided in the bottom and open up the chamber.
- Fill the main body with fresh water and pressurize it by applying air pressure or hydraulic pressure from the top. The connection could be fitted, if not given
- The leaking tube could then be identified when completely dried up
- If the leakage happens from the expansion port of the tube in the tube plate, then it could be expanded slightly, which could arrest the leakage
- The leaking tube could then be plugged from both sides by brass or plastic plugs provided by the manufacturer or could be made as well
- The leaking tube could be replaced as well, depending on its condition
- The leaking tube could be removed by making a bore inside the tube with a drill or a reamer of 0.5mm smaller than the outside diameter of the tube to a depth of the expansion
- Then the tube drawing tool could be inserted and tapped slowly to knock it out from the other end
- The new tube could be installed by inserting the tube expander into both sides of the tube and expanding it
- The wall thickness of reduction= (wall thickness of tube before expansion – wall thickness of tube after expansion) / wall thickness of tube before expansion X100%
- The above value should be between 5-8%